| The
Cellwatch Solution
Data centers, telecommunications sites and other critical power users
require battery supported standby power.
The optimum Battery Monitoring
solution for a typical UPS or telecommunications installation would
be a system permanently wired into the battery
and capable of measuring both voltage and Ohmic Value EVERY
DAY. It should
measure voltage multiple times per day to look for UPS, breaker or cabling
errors. It should look at Ohmic value daily so you get early warning
of impending failure. Both data sets should be stored for later analysis.
The ability to signal, externally to the facility management system,
that a problem either existed or was impending would also be a key feature
of such a system.
Cellwatch fulfills the requirement described above for a reliable,
up-to-date fixed Battery Monitoring System with the following key
features.
-
Measures Voltage on each cell, either 4 or 24 times per day. The
software records data for graphical presentation during THAT day as
well as average data for historical analysis or trending. Also
compares this data continuously with high and low alarm settings for
alarm activation.
- Measures Ohmic Value on each cell, either 1 or 2 times per day. The
software records data for graphical presentation during THAT day as
well as average data for historical analysis or trending. Also compares
this data continuously with high and low alarm settings for alarm
activation.
- Measures the temperature of either the battery room ambient or a
'pilot' cell. Records this figure for graphing as well as comparison
with high and low alarm setting for alarm activation.
- Measures discharge current from a battery string and compares the
data with a discharge alarm limit set in software. In the event of a
discharge, rapidly records all cell voltage data as the battery
discharges for later identification of weak cells under load.
- Supplied with dedicated computer running Windows XP software
and CELLWATCH proprietary application for reporting, recording and
data analysis.
- The system is modular, so if your needs change, CELLWATCH can be
reconfigured or expanded.
- CELLWATCH is a Global product, with manufacturing both in the USA
and in Europe.
- Low voltage DC components. Measurement components never see greater
than 48v nominal DC so battery connections are all low voltage.
Electrical isolation is achieved by plastic fiber optic cable. UL approved
!
Cellwatch components
Cellwatch consists of 3 main building blocks. These are:-
-
Battery Monitoring Unit
(BMU/iBMU). An IBM compatible, industrial
19" server PC, running WindowsXP
as well as CELLWATCH proprietary battery monitoring software.
-
Control Unit
(CU). Interface from the computer's RS485 serial data bus to
CELLWATCH's own proprietary fiber optic network. Also provides up to 4
current sensor and 4 temperature sensor inputs as well as 4 volts free
alarm outputs.
-
Data Collection Module
(DCM). A small electronic measurement instrument capable of measuring
up to 12 volts DC nominal and 25 milliohm Ohmic Value on each
of 4 cell (jar or mono-bloc) inputs. Hence one DCM is required for
every set of 4, 2 volt to 12 volt (nominal) measurement point.
Other components of the CELLWATCH system include 1,000 or 2,500 amp
current sensing 'clamps', solid state temperature probes and
Fiber Optic Network Cable .
CELLWATCH
software is included in a system and is written
for application in the Windows XP operating system to be easy to use and
informative. It has a number of standard graphical reports that provide
the right amount of battery data without overwhelming the user and decimating
rain forests on the way. The intuitive entry screen shows instantly if
something is wrong.
The system is CE qualified in Europe and is certified to meet the requirements
of Underwriter's Laboratories standard for safety in the USA and CSA
in Canada.
To see photographs of our installations, click
here
|
Learn about CELLWATCH software.
Check out our configuration
guide. Look at
installation photographs
Interested in
INTERCONNECTIVITY?
Click here to see one customer's solution. |