System Components

Cellwatch uses data collection modules to monitor your batteries, safely connected by fiber optic.

Cellwatch System Overview

Battery Monitoring Unit (iBMU)

Computer Characteristcs

Operating System

Microsoft Windows Operating System

Software

Cellwatch Applications

Hard Drive

60Gb (min)

Physical Characteristics

Dimensions (H x W x D)

3 1/2” (2U) x 19” x 21”
89mm (2U) x 445mm x 534mm

Enclosure Material

Steel with powder coating

Color

Black

Mounting

19” rack with optional wall mount kit

An industrial 19" rack mount PC, running Microsoft Windows operating system and Cellwatch proprietary battery monitoring software.

Control Unit (CU)

Operating Specifications

Ambient Operating Temperature

0C to 50C / 32F to 122F

Storage Temperature

10C to 80C / 50F to 176F

Power Supply 

Manually switchable 110 VAC or 230 VAC

Power Supply Range

80 VAC to 135 VAC
160 VAC to 270 VAC

Power Supply Frequency

50 Hz to 60 Hz

Power Supply Rating

Max 5VA (15mA quiescent current)

Communications

RS485 Interface

Input and Output with optional jumper
for termination

Max Range

2000 ft (619 m) Total bus length

Fiber Optic Range

150ft (50 m) CU to DCM, DCM to DCM

Max CUs per RS485 bus

31

Alarm Outputs

Output Relays

4 relays, single contact, volts free

Contact Rating

30 vdc @ 8 amps max

Electrical Isolation

1500 vac

Service Life

50 million operations, typical

Protection

Sensing Inputs

Short circuit proof

Insulation Resistance

600 vdc

Sensing Inputs

Temperature sensor

 Solid state probe

Resolution

0.05C

Accuracy

+/-1C

Range

2C to 80C / 35F to 176F

Mounting

5/16” (8mm)

Current Sensor

Solid state, ferrite core clamp

Sensitivity

1mV/1A

Resolution

0.5A (optional 1.25A)

Useful range

 +/- 25 to 1000A (optional 50 to 2500A)

Physical Characteristics

Dimensions

(H x W x D) 4 3⁄4” x 11 7/8” x 11 3/4”

Enclosure material

Steel with powder coating

Color

Pebble Gray

Interface from the computer's RS485 serial data bus to Cellwatch's proprietary fiber optic network. Also provides up to 4 current sensor and 4 temperature sensor inputs as well as four volt--free alarm outputs.

Data Collection Module (DCM)

Voltage Measuring Characteristics

Voltage measuring range

 0 to 60 volts

Resolution

15mV

Accuracy

2 volts nominal source +/-1.0%
6 volts nominal source +/-0.5%

Protection

Transient suppression

Up to 600V, 1 Kw at 100uS pulses
non repetitive

Short Circuit

5 amp max with in line fuses fitted

Reverse Polarity Protection

Any combination in any connection order, for any period of time within the rated voltage

Ohmic value measuring Characteristics

Ohmic value measuring range

0.25 to 25.9 mOhms

Resolution

10 uOhms

Temp coefficient of reading

3 uOhms/C (-5C to 80C / 23F to 176F at nominal 1 uOhm)

Max DCMs per Control Unit

 254

DCM Connections

Fiber Optic Range

Min 6”(150 mm) Max 150 ft (50 m)

Input Cable Lengths

Min 4”(100 mm) Max 16ft 6” (5 m)
Max variation between cables on one unit 6ft 6” (2 m)

Temperatures

Operating temperature

0C to 35C / 32F to 95F

Storage temperature

0C to 80C / 32F to 176F

Power supply nominal

4 x 2v cells up to 4 x 12v jars

Power supply voltage

Min 7 vdc Max 60vdc

Operating current

Quiescent Current

25 mA

During ohmic test

Additional 0.0027A/hr

Physical Characterics

Dimensions (H x W x D)

2 17/32” x 4 5/8” x 1 27/32”
46mm x 64mm x 117mm

Mounting pads

2 “3M Dual Lock”

Enclosure Material

Flame retardant ABS

Color

Black

A small electronic measurement instrument capable of measuring 25 milliohm ohms on each of 4 cell (jar or mono-bloc) inputs. Hence one DCM is required for every set of 4 jars (2 volt to 12 volt nominal).

Generator Extender Kit

Operating Voltage

12 Volts

Operating temperature

 0C to 35C / 32F to 95F

Storage temperature

0C to 80C / 32F to 176F

Communications

Proprietary over CAT5 cable

Max range

4000 ft (1219 m)

Fiber Optic Range

 150 ft (50 m) remote to DCM, DCM to remote

Dimensions (H x W x D)

 

Remote

2 5/8” x 4 5/16” x 1”
65 mm x 110mm x 26mm

Master

2 7/16” x 4 3/4” x 1 3/16”

62 mm x 122mm x 30mm

Monitor all of your ancillary batteries - designed to complement the Cellwatch battery monitoring system by allowing the end-user to monitor generator start batteries, PBX, switch gear, and all critical non-UPS battery systems.
 